Function |
Pick Up Range |
Delay Range |
Notes |
Available current sensor tap ratings |
N/A |
N/A |
40A, 70A, 80A, 100A, 120A, 150A, 200, 225, 300, 400, 600, 800A, 1000A, 1200A, 1600A, 2000A, 2400A, 2500A, 3000A, 3200A, 4000A, 4200A, 5000A, 6000A |
Long-time (overload) protection |
From 25% to 110% of the current sensor tap rating |
MIN (5 sec), INT (13 sec), MAX (27 sec) or custom value between 1 and 30 seconds. Delay is reverse I2t and defined by time to trip at 600% of the long-time pickup value |
|
Short-time protection |
From 150% to 1000% of the long-time pickup value. |
Selectable constant or reverse I2t ramp with delays of .070, .100, .150, .200, .300, .400, .500, or .600 seconds. |
Function can be defeated provided that the Instantaneous protection band is enabled.Delay can be selected either as a fixed delay or reverse I2t. |
Instantaneous protection |
From 150 to 1200% of the long-time pickup value. |
Trips breaker in less than .050 seconds. |
Function can be defeated provided that Short-time protection is enabled. |
Ground Fault protection |
From 10% to 200% of the sensor tap rating, provided that this value does not exceed 1200A. Increments are of 5% of the sensor tap rating up to 100% of tap rating. Above 100% of tap rating, increments are in 10% of tap rating. |
Selectable constant or reverse I2t ramp with delays of .100, .150, .200, .300, .400 or .500 seconds. |
Function can be defeated.Delay can be selected either as a fixed delay or reverse I2t. |
Phase Imbalance protection. |
From 15% to 50% ratio of minimum /maximum phase current. |
Between 1 and 90 seconds |
Function can be defeated. |
flashSAFE Instantaneous Pickup |
Same as Instantaneous |
Trips breaker in less than .050 seconds. |
May be defeated. Must be lower than the previously entered instantaneous pickup. May be enabled even if instantaneous is defeated. |
flashSAFE Ground fault pickup. |
Same as Ground Fault |
Fixed at .100 seconds w/ no I2t ramp |
May be defeated. Must be lower than the previously entered ground fault pickup. May be enabled even if ground fault is defeated |
Long-time thermal memory |
ON or OFF |
N/A |
|
Ground-fault thermal memory |
ON or OFF |
N/A |
|